Why chiller efficiency matters
In large buildings in hot climates, chilled-water plants are often the largest single electricity user: 40–60% of a mall’s or office tower’s consumption in Malaysia, Singapore or the Gulf. The IEA’s Future of Cooling report expects global cooling demand to keep rising, so the efficiency of the plant that makes the cold water matters a great deal for bills and grids.
The industry measures that efficiency in kW per ton of refrigeration (kW/TR): electrical power in, per unit of cooling out. Lower is better. This calculator turns capacity, average load, hours and kW/TR into annual kWh, cost and CO₂, and compares the existing chiller with a more efficient replacement.
The formula
COP = 3.517 ÷ kW/TR EER (Btu/Wh) = 12 ÷ kW/TR 1 TR = 12,000 Btu/h = 3.517 kW
Saving = TR·h × (kW/TR_old − kW/TR_new) × price Payback = new chiller cost ÷ annual saving
Auxiliaries are the chilled-water and condenser-water pumps and the cooling-tower fans, usually 0.15–0.35 kW/TR together. Air-cooled chillers have no condenser pumps or towers, only fans already counted in their kW/TR.
Worked example
The defaults describe a 500 TR office chiller from the 1990s at 0.85 kW/TR, with 0.25 kW/TR of pumps and towers, an average load of 65% and 4,500 operating hours, paying 0.14 per kWh.
- Cooling delivered: 500 × 0.65 × 4,500 = 1.46 million ton-hours.
- Electricity: 1.46 million × (0.85 + 0.25) = 1.61 GWh, costing about 225,000 a year. That is 0.154 per ton-hour.
- The chiller’s COP is 3.517 ÷ 0.85 = 4.14; the whole plant runs at a COP of 3.2.
- A magnetic-bearing centrifugal at 0.52 kW/TR cuts consumption by 483,000 kWh, saving about 67,600 a year. At 450 per TR installed (225,000), the payback is about 3.3 years. On Malaysia’s grid (about 600 g CO₂/kWh lifecycle) it also avoids roughly 290 t of CO₂ a year.
Typical efficiencies
| Chiller type | Full-load kW/TR | Typical IPLV kW/TR | COP (full load) |
|---|---|---|---|
| Air-cooled scroll / screw | 1.0–1.3 | 0.75–1.0 | 2.7–3.5 |
| Water-cooled screw | 0.60–0.75 | 0.45–0.60 | 4.7–5.9 |
| Water-cooled centrifugal | 0.50–0.60 | 0.35–0.50 | 5.9–7.0 |
| Magnetic-bearing centrifugal | 0.50–0.58 | 0.30–0.40 | 6.1–7.0 |
| Centrifugal from the 1990s | 0.75–0.95 | 0.60–0.80 | 3.7–4.7 |
Ranges are indicative; check the AHRI-certified rating of a specific model. Minimum efficiencies in ASHRAE 90.1 tighten with each edition.
How to read the results
- Annual electricity cost is the headline. Compare it with the price of a new chiller: it is often similar to one year of running cost.
- Plant efficiency includes pumps and towers. A whole plant at under 0.75 kW/TR is considered efficient in the tropics; above 1.0 kW/TR there is usually a lot to gain.
- Cost per ton-hour lets you charge cooling to tenants or compare with district cooling offers.
- The doughnut shows the share of pumps and towers, which variable-speed drives and better controls can cut substantially. The motor energy savings calculator models pump drives.
Tips beyond replacing the chiller
- Raise the chilled-water temperature as far as comfort and dehumidification allow; each 1 °C improves chiller efficiency by roughly 2–3%.
- Lower the condenser-water temperature with well-maintained towers and clean condenser tubes.
- Add variable-speed drives to pumps and tower fans, and avoid running more chillers than the load needs.
- Shift cooling with thermal storage where a time-of-use tariff applies; see the time-of-use savings calculator.
Limitations
A single average kW/TR hides real behaviour. Efficiency changes with load, condenser-water temperature and chilled-water set point, so for investment decisions use IPLV/NPLV or, better, an hourly simulation with measured loads. Demand charges are not included, though a more efficient plant also lowers peak kW; the demand charge calculator estimates that saving. Refrigerant changes, maintenance savings and incentives are left out.
Method & assumptions
Cooling delivered (ton-hours) = capacity (TR) × average load × hours. Electricity = ton-hours × (chiller kW/TR + auxiliary kW/TR). COP = 3.517 ÷ kW/TR; EER = 12 ÷ kW/TR. Saving = ton-hours × (old − new kW/TR) × price; payback = new chiller cost ÷ annual saving.
Frequently asked questions
How do I convert kW/TR to COP?
What is a good kW per ton for a chiller?
How much electricity does a 500-ton chiller use?
What is a refrigeration ton?
Is it worth replacing an old chiller?
What is IPLV?
Sources & references