How demand charges work
A household pays for kWh. A factory, office or shop usually pays twice: once for the energy (kWh) and again for the highest power it drew during the month (kW, sometimes kVA). The utility’s meter averages power over 15- or 30-minute intervals and remembers the highest one. That single interval sets the demand charge for the whole month.
The reason is cost. Cables, transformers and generation must be sized for the peak, whether it lasts all day or ten minutes. For a site with a short, high peak, demand charges can be a third to two-thirds of the bill. This calculator splits the bill into energy, demand and fixed parts, computes the load factor and the effective price per kWh, and shows what a lower peak is worth, including the battery needed to achieve it.
The formula
Peak-shaving saving = (billed kW before − billed kW after) × demand charge Battery energy ≈ kW reduction × peak duration ÷ 0.9 usable
Worked example
The defaults describe a factory using 120,000 kWh a month with a 450 kW peak, paying 0.10 per kWh, 15 per kW-month and a 100 fixed charge.
- Load factor: 120,000 ÷ (450 × 730) = 37%. The average load is 164 kW, a little over a third of the peak.
- Energy charges: 12,000. Demand charges: 450 × 15 = 6,750, which is 36% of the 18,850 bill.
- Effective price: 18,850 ÷ 120,000 = 0.157 per kWh, 57% above the energy rate.
- Shaving the peak by 60 kW saves 900 a month, 10,800 a year.
- If the peak lasts about 1.5 hours, a battery needs about 100 kWh. At 350 per kWh it costs about 35,000 and pays back from demand savings alone in about 3.2 years.
The last preset shows the catch with ratchets. An EV depot with an 80% ratchet and a 750 kW peak from earlier in the year is billed for 600 kW anyway. Shaving this month’s peak from 600 to 450 kW saves nothing until the old peak rolls off.
Typical values
| Site type | Typical load factor | Demand share of bill (at 10–20 per kW-month) |
|---|---|---|
| Cold store, data centre, 24/7 process | 70–90% | 15–25% |
| Three-shift factory | 55–75% | 20–30% |
| Single-shift factory | 30–45% | 30–45% |
| Office or school | 25–40% | 30–50% |
| EV fast-charging site | 5–20% | 50–80% |
How to read the results
- Effective price is what each kWh really costs once demand charges are spread over it. Use it, not the energy rate, to value efficiency or solar savings.
- Load factor below about 40% means demand charges dominate and peak management is worth looking at.
- The table of shaving options shows savings for 5–30% peak reductions. The first few percent are usually cheap, coming from load scheduling, while deeper cuts need storage.
- Battery payback counts demand savings only. A battery that also stores solar or shifts energy to cheaper hours earns more; see the time-of-use savings calculator and the LCOS calculator.
Tips to cut the peak
- Find the peak first. Interval data from the utility or a logger shows when it happens: often Monday morning start-up, a hot afternoon or a shift change.
- Stagger start-ups of compressors, chillers, ovens and furnaces after a shutdown.
- Shed non-critical loads automatically when demand nears a set limit.
- Improve power factor if the tariff bills kVA demand. The power factor correction calculator shows the saving.
- Charge EV fleets smartly so vehicles do not all start charging at once.
Limitations
Tariff structures vary widely: on-peak only demand, seasonal rates, coincident-peak charges, contracted capacity with penalties for exceeding it, or demand billed in kVA. Enter the numbers that match your bill and treat the result as an estimate. The battery sizing assumes one peak per day of the given duration and ignores degradation and round-trip losses beyond the usable-capacity factor.
Method & assumptions
Load factor = monthly kWh ÷ (peak kW × 730 h). Bill = kWh × energy price + billed kW × demand charge + fixed charge. Billed kW = max(actual peak, ratchet % × highest peak of the last 12 months). Effective price = bill ÷ kWh = energy price + demand charge ÷ (load factor × 730). Peak-shaving saving = reduction in billed kW × demand charge. Battery energy ≈ kW reduction × peak duration ÷ 0.9 usable.
Frequently asked questions
What is a demand charge on an electricity bill?
How is load factor calculated?
How do I reduce demand charges?
What is a demand ratchet?
Is a battery worth it for peak shaving?
Why is my effective price per kWh higher than the energy rate?
Sources & references
Embed this calculator