Electrical engineering calculator

Power factor correction calculator: capacitor kVAr, µF and savings

Size the capacitor bank (kVAr and µF per phase) that lifts a load from its present power factor to a target, then see the drop in current and kVA, the freed transformer capacity, the cut in cable losses and the money saved on kVA demand charges, kVArh charges or low-PF surcharges, with payback.

Editable share link Branded PDF report Free · no sign-up

Results

Lifting 250 kW from PF 0.78 to 0.95 needs 118.4 kVAr of capacitors (a 125 kVAr bank). Current drops from 463 A to 380 A, freeing 57 kVA of supply capacity. Savings of about 786 € a month pay back the bank in 4.8 months.
Capacitor required
118.4kVAr
nearest standard bank: 125 kVAr
Capacitance per phase (delta)
785µF
2,355 µF per phase in star
Current before
463A
Current after
380A
−18%
Apparent power before
321kVA
Apparent power after
263kVA
Reactive power before
201kVAr
82 kVAr after
Cut in I²R losses
33%
Tariff saving per month
€688
57.4 kVA less maximum demand
Loss saving per month
€97.76
Capacitor bank cost
€3,750
Simple payback
4.8months
9,432 € saved per year
kVAr needed vs target power factor
Current and kVA before and after

kVAr per kW multiplier (tan φ1 − tan φ2)

Present PFto 0.9to 0.92to 0.95to 0.98to 1
0.60.8490.9071.0051.131.333
0.650.6850.7430.840.9661.169
0.70.5360.5940.6920.8171.02
0.750.3980.4560.5530.6790.882
0.80.2660.3240.4210.5470.75
0.850.1350.1940.2910.4170.62
0.9—0.0580.1560.2810.484
  • Where many variable-speed drives, inverters or other harmonic sources are present, use detuned (reactor-protected) capacitor banks or active filters to avoid resonance.
  • Correct to 0.95–0.98 rather than 1.0: at light load a fixed bank can push the PF leading and raise the voltage. Automatic stepped banks track the load.

Why power factor costs money

Induction motors, transformers and fluorescent ballasts need magnetising current that flows back and forth without doing any work. This reactive power (kVAr) adds to the current in every cable, switchboard and transformer between the power station and your machine. The power factor (PF) is the share of apparent power (kVA) that does useful work (kW). A PF of 0.78 means you draw 28% more current than a purely resistive load of the same kW would.

Utilities pass that cost on in one of three ways. They bill maximum demand in kVA instead of kW. They charge for reactive energy (kVArh) above a free allowance. Or they add a surcharge when the monthly PF falls below a threshold such as 0.85 or 0.9. A capacitor bank on site supplies the reactive power locally, so it no longer flows through the meter.

The formula

φ = arccos(PF) Q_c = P × (tan φ1 − tan φ2) (kVAr)

C per phase (delta) = Q_c ÷ (3 × 2πf × V_LL²) C per phase (star) = 3 × C_delta

S = P ÷ PF I = S ÷ (√3 × V_LL) Loss reduction = 1 − (PF1 ÷ PF2)²

The table under the results gives the kVAr-per-kW multiplier (tan φ1 − tan φ2) for common starting and target power factors. This is the same table printed in every capacitor catalogue.

Worked example

The defaults describe a factory with an average load of 250 kW at PF 0.78 on a 400 V, 50 Hz supply, billed 12 per kVA of maximum demand each month.

  • tan φ1 = 0.802 and tan φ2 (PF 0.95) = 0.329, so Q_c = 250 × 0.473 = 118 kVAr. The next standard size is a 125 kVAr automatic bank.
  • Per-phase capacitance for a delta bank: 118,400 ÷ (3 × 314.2 × 400²) = 785 µF.
  • Apparent power falls from 321 kVA to 263 kVA and current from 463 A to 380 A. The supply transformer gains 57 kVA of headroom.
  • Demand charge saving: 57.4 kVA × 12 = 688 per month. With 2% losses in your own network, the 33% loss reduction saves about another 98 a month at 0.15/kWh over 400 hours.
  • At 30 per kVAr the bank costs 3,750 and pays back in about five months.

The second and third presets show the other billing methods. Under a reactive-energy tariff with a free allowance of tan φ = 0.4 (a PF of about 0.93, a common European rule), 500 kW at PF 0.82 pays for about 60,000 kVArh a month. The third preset models a surcharge of 1.5% of the bill for every 0.01 below PF 0.85, a structure used by several Asian utilities, including TNB in Malaysia for many customer classes.

Typical power factors

Load Typical PF
Induction motor, full load 0.80–0.90
Induction motor, 50% load 0.65–0.80
Induction motor, idling 0.10–0.30
Welding transformer 0.40–0.60
Variable-speed drive (input) 0.92–0.97 displacement, lower true PF with harmonics
LED lighting with good driver 0.90–0.98
Resistive heating 1.0

Lightly loaded motors are the main cause of poor plant power factor, so right-sizing motors helps as much as capacitors do. The motor energy savings calculator covers that side.

How to read the results

  • Capacitor required is the kVAr needed at your average load. Size an automatic bank so its steps cover your minimum and maximum load.
  • Current after shows the relief on cables and switchgear, often enough to postpone a transformer upgrade. Check transformer headroom with the transformer sizing calculator.
  • Tariff saving depends entirely on how you are billed. If your bill shows no kVA, kVArh or PF line, the saving is limited to losses.
  • Simple payback for capacitor banks is often under two years where reactive power is billed.

Limitations

The calculation uses a single average load. Real plants vary through the day, so the reactive charge depends on the integrated kVArh or the peak kVA in the billing period. Harmonics are not modelled: with many drives or inverters, plain capacitors can create resonance, so use detuned banks or active filters. Capacitor voltage rating, discharge resistors and protection must follow IEC 60831 or your national code. For a simple kVA ↔ kW conversion use kVA to kW.

Method & assumptions

Qc = P × (tan φ1 − tan φ2), φ = arccos(PF). Capacitance per phase for a delta-connected three-phase bank: C = Qc ÷ (3 × 2πf × VLL²); a star-connected bank needs three times this capacitance. Current I = P ÷ (√3 × V × PF). Losses scale with I², so they fall by 1 − (PF1/PF2)². Tariff savings depend on the billing method you select.

Frequently asked questions

How do I calculate the kVAr needed for power factor correction?
Multiply the active power by the difference of the tangents: Qc = kW × (tan φ1 − tan φ2), where φ = arccos(PF). To raise 250 kW from PF 0.78 to 0.95 you need 250 × (0.802 − 0.329) = 118 kVAr, so a 125 kVAr bank.
How do I convert kVAr to microfarads?
For a three-phase delta-connected bank, C per phase = Q ÷ (3 × 2πf × V²) with Q in VAr and V the line voltage. 118 kVAr at 400 V and 50 Hz gives about 785 µF per phase. A star-connected bank needs three times that capacitance per phase, at a lower voltage rating.
Does power factor correction reduce my electricity bill?
Only if your tariff charges for reactive power or for kVA demand, or if you pay a low-power-factor surcharge. Most commercial and industrial tariffs do one of these. Households are billed for kWh only, so a capacitor will not lower a home bill. The small I²R loss saving in your own cables is real but modest.
What power factor should I aim for?
0.95–0.98 is the usual target. Going to exactly 1.0 costs extra kVAr for little gain and risks a leading power factor when the load drops. Automatic stepped banks switch capacitors in and out to follow the load.
How much current does power factor correction save?
Current is proportional to 1 ÷ PF for the same kW. Improving from 0.78 to 0.95 cuts current by 18%, and because losses go with the square of current, I²R losses in cables and transformers fall by about a third.
When do I need a detuned capacitor bank?
When harmonic-producing loads (variable-speed drives, UPS, LED drivers, rectifiers) make up more than about 15–25% of the load. Plain capacitors can resonate with the supply transformer at a harmonic frequency and fail early. Detuned banks add a series reactor, typically tuned to 189 Hz (7%) on 50 Hz systems.

Sources & references

  1. IEC 60831-1 — Shunt power capacitors of the self-healing type for AC systems up to 1,000 V
  2. IEEE Std 1036 — Guide for the Application of Shunt Power Capacitors
  3. US DOE — Reducing Power Factor Cost (Motor Systems Tip Sheet #8)
  4. Schneider Electric — Electrical Installation Guide, chapter L: Power factor correction

Embed this calculator

Free for blogs, installers, schools and NGOs. Copy the code below; it updates itself automatically.