Why power factor costs money
Induction motors, transformers and fluorescent ballasts need magnetising current that flows back and forth without doing any work. This reactive power (kVAr) adds to the current in every cable, switchboard and transformer between the power station and your machine. The power factor (PF) is the share of apparent power (kVA) that does useful work (kW). A PF of 0.78 means you draw 28% more current than a purely resistive load of the same kW would.
Utilities pass that cost on in one of three ways. They bill maximum demand in kVA instead of kW. They charge for reactive energy (kVArh) above a free allowance. Or they add a surcharge when the monthly PF falls below a threshold such as 0.85 or 0.9. A capacitor bank on site supplies the reactive power locally, so it no longer flows through the meter.
The formula
C per phase (delta) = Q_c ÷ (3 × 2πf × V_LL²) C per phase (star) = 3 × C_delta
S = P ÷ PF I = S ÷ (√3 × V_LL) Loss reduction = 1 − (PF1 ÷ PF2)²
The table under the results gives the kVAr-per-kW multiplier (tan φ1 − tan φ2) for common starting and target power factors. This is the same table printed in every capacitor catalogue.
Worked example
The defaults describe a factory with an average load of 250 kW at PF 0.78 on a 400 V, 50 Hz supply, billed 12 per kVA of maximum demand each month.
- tan φ1 = 0.802 and tan φ2 (PF 0.95) = 0.329, so Q_c = 250 × 0.473 = 118 kVAr. The next standard size is a 125 kVAr automatic bank.
- Per-phase capacitance for a delta bank: 118,400 ÷ (3 × 314.2 × 400²) = 785 µF.
- Apparent power falls from 321 kVA to 263 kVA and current from 463 A to 380 A. The supply transformer gains 57 kVA of headroom.
- Demand charge saving: 57.4 kVA × 12 = 688 per month. With 2% losses in your own network, the 33% loss reduction saves about another 98 a month at 0.15/kWh over 400 hours.
- At 30 per kVAr the bank costs 3,750 and pays back in about five months.
The second and third presets show the other billing methods. Under a reactive-energy tariff with a free allowance of tan φ = 0.4 (a PF of about 0.93, a common European rule), 500 kW at PF 0.82 pays for about 60,000 kVArh a month. The third preset models a surcharge of 1.5% of the bill for every 0.01 below PF 0.85, a structure used by several Asian utilities, including TNB in Malaysia for many customer classes.
Typical power factors
| Load | Typical PF |
|---|---|
| Induction motor, full load | 0.80–0.90 |
| Induction motor, 50% load | 0.65–0.80 |
| Induction motor, idling | 0.10–0.30 |
| Welding transformer | 0.40–0.60 |
| Variable-speed drive (input) | 0.92–0.97 displacement, lower true PF with harmonics |
| LED lighting with good driver | 0.90–0.98 |
| Resistive heating | 1.0 |
Lightly loaded motors are the main cause of poor plant power factor, so right-sizing motors helps as much as capacitors do. The motor energy savings calculator covers that side.
How to read the results
- Capacitor required is the kVAr needed at your average load. Size an automatic bank so its steps cover your minimum and maximum load.
- Current after shows the relief on cables and switchgear, often enough to postpone a transformer upgrade. Check transformer headroom with the transformer sizing calculator.
- Tariff saving depends entirely on how you are billed. If your bill shows no kVA, kVArh or PF line, the saving is limited to losses.
- Simple payback for capacitor banks is often under two years where reactive power is billed.
Limitations
The calculation uses a single average load. Real plants vary through the day, so the reactive charge depends on the integrated kVArh or the peak kVA in the billing period. Harmonics are not modelled: with many drives or inverters, plain capacitors can create resonance, so use detuned banks or active filters. Capacitor voltage rating, discharge resistors and protection must follow IEC 60831 or your national code. For a simple kVA ↔ kW conversion use kVA to kW.
Method & assumptions
Qc = P × (tan φ1 − tan φ2), φ = arccos(PF). Capacitance per phase for a delta-connected three-phase bank: C = Qc ÷ (3 × 2πf × VLL²); a star-connected bank needs three times this capacitance. Current I = P ÷ (√3 × V × PF). Losses scale with I², so they fall by 1 − (PF1/PF2)². Tariff savings depend on the billing method you select.
Frequently asked questions
How do I calculate the kVAr needed for power factor correction?
How do I convert kVAr to microfarads?
Does power factor correction reduce my electricity bill?
What power factor should I aim for?
How much current does power factor correction save?
When do I need a detuned capacitor bank?
Sources & references
- IEC 60831-1 — Shunt power capacitors of the self-healing type for AC systems up to 1,000 V
- IEEE Std 1036 — Guide for the Application of Shunt Power Capacitors
- US DOE — Reducing Power Factor Cost (Motor Systems Tip Sheet #8)
- Schneider Electric — Electrical Installation Guide, chapter L: Power factor correction