A nuclear power station is a steam plant with an unusual boiler. The turbine hall, generator and cooling towers look much like those at a coal or gas plant. What differs is the heat source: a core of uranium fuel in which atoms split in a controlled chain reaction. This guide walks through the physics, the main reactor designs in use, why reactors need cooling even when switched off, and what the newer Generation III+ designs changed. For the economics and the policy debate, see Nuclear Power: Pros and Cons.
Fission in one paragraph
When a slow neutron hits a uranium-235 nucleus, the nucleus can absorb it, become unstable and split into two lighter fragments (fission products such as caesium, strontium and iodine isotopes). Each split releases about 200 MeV of energy, mostly as the kinetic energy of the fragments, which turns into heat as they slam into surrounding atoms. It also frees two or three new neutrons. If on average exactly one of those neutrons causes another fission, the reaction sustains itself at a steady rate. Operators call this state critical, which in reactor language simply means stable, not dangerous. See nuclear fission in the glossary.
Natural uranium contains only 0.711% U-235; the rest is U-238, which rarely fissions with slow neutrons. Most reactors therefore use fuel enriched to 3–5% U-235, packed as ceramic uranium dioxide pellets into zirconium-alloy tubes. Some U-238 absorbs neutrons and turns into plutonium-239, which also fissions, so by the end of its life a fuel assembly gets a good share of its energy from plutonium. The nuclear fuel cycle guide covers how fuel is made.
The parts of a reactor core
Moderator. Neutrons from fission are fast. U-235 captures slow (thermal) neutrons far more readily, so most reactors slow them down by letting them bounce off light atoms. Ordinary water, heavy water and graphite are the common moderators.
Control rods. Rods containing neutron absorbers such as boron, cadmium, hafnium or silver-indium-cadmium slide into the core to soak up neutrons. Pushing them in reduces power; dropping them fully (a scram) stops the chain reaction within seconds. PWRs also dissolve boric acid in the cooling water to trim reactivity over a fuel cycle.
Coolant. Something has to carry heat out of the core: water in most reactors, carbon dioxide or helium in gas-cooled designs, liquid sodium or lead in fast reactors.
Pressure vessel and containment. In light-water reactors the core sits in a steel pressure vessel with walls around 20–25 cm thick, inside a reinforced concrete containment building designed to hold in radioactive material even if the cooling circuit breaks.
A useful safety property of water-moderated reactors is a negative temperature coefficient: if the core heats up, the water becomes less dense, moderates less, and power falls by itself.
The main reactor types
| Design | Moderator / coolant | Fuel | Pressure, outlet temp. | Where | Share of fleet (approx.) |
|---|---|---|---|---|---|
| PWR (pressurised water) incl. VVER | Light water / light water | 3–5% enriched UO₂ | ~155 bar, ~325 °C | US, France, China, Russia, Korea, Japan | ~70% |
| BWR (boiling water) | Light water / light water | 3–5% enriched UO₂ | ~70 bar, ~285 °C | US, Japan, Sweden, Finland | ~15% |
| PHWR (CANDU) | Heavy water / heavy water | Natural uranium | ~100 bar, ~310 °C | Canada, India, Argentina, Romania | ~10% |
| RBMK | Graphite / boiling light water | ~2% enriched | ~70 bar | Russia only (a few units left) | under 2% |
| AGR / gas-cooled | Graphite / CO₂ | Enriched UO₂ | ~40 bar, ~640 °C | UK | under 2% |
Shares are rounded from IAEA PRIS counts. In a PWR, the primary water never boils. It carries heat to steam generators, where a separate secondary loop boils and feeds the turbine, so the turbine never sees radioactive water. A BWR is simpler, with one loop, but its turbine hall is mildly radioactive during operation. CANDU reactors use heavy water, which absorbs so few neutrons that natural uranium works as fuel, and they refuel while running. The RBMK, the Chernobyl design, had a positive void coefficient at low power: steam bubbles increased reactivity instead of reducing it. Combined with a flawed control rod design and a badly run test, that produced the 1986 disaster. The remaining RBMKs were modified afterwards.
From heat to electricity
Light-water reactors run their steam at around 70 bar and 280–290 °C, much cooler than the 600 °C of an ultra-supercritical coal plant. Lower steam temperature means lower efficiency, typically 33–37%. A large unit producing 3,400 MW of heat sends around 1,150 MW to the grid and rejects about 2,250 MW to the sea, a river or cooling towers. That is why so many plants sit on coasts.
Reactors usually run flat out because their fuel is cheap and their capital cost is high. The world fleet’s average capacity factor is around 80%, and the best US plants have averaged above 90% for two decades. French reactors do follow load daily, ramping between roughly 50% and 100% power, so baseload operation is a choice, not a physical limit. Check what that means for annual output in the capacity factor calculator.
Decay heat: why “off” is not cold
Shutting down the chain reaction does not stop heat production. The fission products in the fuel are radioactive and keep decaying.
| Time after shutdown | Decay heat (share of full thermal power) | For a 3,400 MWth reactor |
|---|---|---|
| 1 second | ~6–7% | ~220 MW |
| 1 hour | ~1.5% | ~50 MW |
| 1 day | ~0.5% | ~17 MW |
| 1 week | ~0.2% | ~7 MW |
Approximate values from standard decay heat curves. Without cooling, 17 MW is enough to boil off water and overheat the fuel within hours. That is what happened at Fukushima Daiichi in March 2011, when the tsunami knocked out power to the cooling pumps of three operating units. Spent fuel also has to sit in cooling pools for years before it can move to dry casks; see Nuclear Waste: The Facts.
Safety systems, layer by layer
Reactor safety follows defence in depth: several independent barriers and systems, each assumed to fail sometimes.
- Physical barriers: the ceramic fuel pellet, the cladding, the reactor coolant boundary, and the containment building.
- Shutdown: control rods that drop by gravity or are driven in, plus backup boron injection.
- Emergency core cooling: high- and low-pressure injection pumps, accumulators that discharge borated water without power, and backup diesel generators.
- Hydrogen control: recombiners that stop the hydrogen made by overheated cladding from building up.
- Filtered venting and core catchers in newer designs to limit releases even after core melt.
Generation III+: what changed
Reactors designed after the 1990s add more redundancy and, in several designs, passive safety: systems that rely on gravity, natural circulation and stored pressure instead of pumps and operators.
| Design | Vendor | Size (MWe) | Passive or active | Examples in operation |
|---|---|---|---|---|
| EPR | EDF / Framatome | ~1,650 | Active, 4 redundant trains, core catcher | Taishan 1–2 (China), Olkiluoto 3 (Finland, 2023), Flamanville 3 (France, grid 2024) |
| AP1000 | Westinghouse | ~1,100 | Passive cooling for 72 h | Sanmen, Haiyang (China), Vogtle 3–4 (US, 2023–2024) |
| APR1400 | KEPCO / KHNP | ~1,400 | Mostly active | Shin Kori, Saeul (Korea), Barakah 1–4 (UAE) |
| Hualong One (HPR1000) | CNNC / CGN | ~1,100 | Active + passive | Fuqing 5–6 (China), Karachi K-2/K-3 (Pakistan) |
| VVER-1200 | Rosatom | ~1,200 | Active + passive | Novovoronezh II, Leningrad II, Ostrovets (Belarus) |
The first Western units ran years late and billions over budget; Vogtle 3 and 4 cost more than $30 billion in total. Chinese and Korean builds have been much faster, often five to six years from first concrete. Smaller designs are covered in Small Modular Reactors Explained.
The short version
- A reactor is a heat source for a steam turbine: fission of U-235 (and bred Pu-239) heats water.
- Moderators slow neutrons, control rods absorb them, and coolant carries heat away. Water-cooled cores naturally lose power as they heat up.
- PWRs dominate the fleet; BWRs, CANDUs and a few legacy designs make up the rest.
- Decay heat means cooling must continue for days after shutdown and years for spent fuel.
Nuclear generated about 2,770 TWh in 2024, around 9% of the world’s electricity (Ember). See which countries rely on it most on the nuclear energy hub, the nuclear technology page and country profiles such as France.
Calculators for this topic
Frequently asked questions
How does a nuclear reactor produce electricity?
Can a nuclear reactor explode like a bomb?
Why do reactors need cooling after they shut down?
How many nuclear reactors are there in the world?
What is the difference between a PWR and a BWR?
How efficient is a nuclear power plant?
Sources & references
Figures in this guide are typical ranges drawn from the sources above; your own numbers depend on location, prices and equipment. Use the linked calculators for site-specific estimates.