Electrical engineering calculator

Short-circuit current calculator: fault level at the transformer and cable end

Three-phase prospective short-circuit current (kA) and peak current at the LV terminals of a transformer and at the end of a cable, from the upstream fault level, transformer kVA and impedance, cable size, length and material, using the IEC 60909 method.

Editable share link Branded PDF report Free · no sign-up

Results

The prospective three-phase fault current is 23.6 kA at the transformer LV terminals (peak 56.5 kA) and 18.6 kA at the cable end. Protective devices need a breaking capacity of at least 25 kA at the main board and 20 kA at the end of the cable.
Ik3 at transformer terminals
23.6kA
25.3 kA with an infinite source
Peak current ip (terminals)
56.5kA
κ = 1.69
Ik3 at cable end
18.6kA
Peak current ip (cable end)
37.9kA
Line-to-line fault Ik2 (cable end)
16.1kA
Transformer full-load current
1,443A
Breaking capacity, main board
25kA
next standard Icu/Icn
Breaking capacity, cable end
20kA
Fault current vs cable length

Impedance per phase (referred to LV)

ElementR (mΩ)X (mΩ)Z (mΩ)
Upstream network0.070.670.67
Transformer1.229.529.6
Cable2.232.43.27
Total to cable end3.5112.5913.07
  • Maximum three-phase symmetrical fault current per IEC 60909-0 with voltage factor c and conductors at 20 °C. Motor contribution and the transformer correction factor KT are neglected (KT is close to 1 for uk ≤ 6%).
  • Single-phase earth-fault current depends on the zero-sequence impedance and the earthing system; at the transformer terminals of a Dyn unit it is about the same as Ik3, and it falls faster along the cable.

Why fault current matters

When phases short together, the only thing limiting the current is the impedance of the network between the source and the fault. Near a large transformer that can be tens of kiloamps. Every breaker and fuse must be able to interrupt the highest current it might see; if it cannot, it can explode instead of clearing the fault. Busbars and cable supports must also survive the peak electromagnetic forces of the first half-cycle. Fault current is therefore one of the first numbers in any LV design, alongside load current and voltage drop.

This calculator follows the IEC 60909 impedance method for a radial LV system: medium-voltage network, distribution transformer, then a cable run to a sub-board. It returns the maximum three-phase fault current at both points, the peak current, the line-to-line fault current and the minimum standard breaking capacity.

The formula

Network: Z_Q = c·U² ÷ S″kQ (X/R ≈ 10) Transformer: Z_T = u_k·U² ÷ S_n R_T = P_k·U² ÷ S_n² X_T = √(Z_T² − R_T²) Cable: R_C = ρ·L ÷ (A·n) X_C = x′·L ÷ n

I″k3 = c·U ÷ (√3 · |Z_Q + Z_T + Z_C|) i_p = κ·√2·I″k3 κ = 1.02 + 0.98·e^(−3R/X) I″k2 = (√3 ÷ 2)·I″k3

U is the LV line voltage, ρ is 0.0178 Ω·mm²/m for copper and 0.0286 for aluminium (20 °C, as IEC 60909 requires for maximum currents), A is the cross-section, n the number of parallel cables per phase and x′ the cable reactance, about 0.08 mΩ/m for multicore cables.

Worked example

The defaults model a 1,000 kVA, 6% transformer (7.6 kW load losses) fed from a 250 MVA MV network, with a 400 V secondary feeding a sub-board through 60 m of two parallel 240 mm² copper cables.

  • Network impedance referred to 400 V: 1.05 × 400² ÷ 250 MVA = 0.67 mΩ.
  • Transformer impedance: 0.06 × 400² ÷ 1,000 kVA = 9.6 mΩ, of which R = 1.22 mΩ and X = 9.52 mΩ.
  • At the LV terminals: |Z| ≈ 10.3 mΩ, so I″k3 = 1.05 × 400 ÷ (1.732 × 10.3 mΩ) ≈ 23.6 kA. With X/R ≈ 7.8, κ = 1.69 and the peak current is 56.5 kA.
  • The cable adds 2.2 mΩ of resistance and 2.4 mΩ of reactance, and the fault current at the sub-board falls to 18.6 kA.
  • The main LV breaker needs at least a 25 kA breaking capacity; devices at the sub-board need 20 kA.

The simple rule I_n ÷ u_k gives 24.1 kA, or 25.3 kA with c = 1.05, close to the full result because a 250 MVA network is stiff compared with a 1 MVA transformer.

Typical values at 400 V transformer terminals

Transformer u_k Full-load current I″k3 (infinite source, c = 1.05)
250 kVA 4% 361 A ≈ 9.5 kA
400 kVA 4% 577 A ≈ 15 kA
630 kVA 4% 909 A ≈ 24 kA
1,000 kVA 6% 1,443 A ≈ 25 kA
1,600 kVA 6% 2,309 A ≈ 40 kA
2,500 kVA 6% 3,608 A ≈ 63 kA

Two transformers in parallel on one busbar roughly double the fault level, which is a common reason for switchgear upgrades.

How to read the results

  • Ik3 at transformer terminals sets the breaking capacity of the main LV switchboard.
  • Peak current ip is the value to check against the busbar system’s rated peak withstand current (Ipk).
  • Ik3 at cable end sets the rating for downstream boards. The chart shows how fast fault current falls with distance.
  • Line-to-line Ik2 is lower and is sometimes used to check that protection still trips fast enough.

Limitations

The result is the maximum symmetrical three-phase current. It leaves out motor contribution, generator sources, the transformer correction factor K_T (close to 1 for normal transformers), and conductor heating during the fault. Earth-fault current depends on the earthing system (TN, TT, IT) and zero-sequence impedance and needs its own calculation, especially for checking disconnection times. For final designs, use dedicated software or a full IEC 60909 or IEEE 551 study. Size the cable for load and voltage drop with the cable size calculator.

Method & assumptions

Source impedance ZQ = c U² ÷ S″kQ (X/R = 10). Transformer ZT = uk U² ÷ Sn, RT = Pk U² ÷ Sn². Cable R = ρ L ÷ (A × n), X = x′ L ÷ n. Symmetrical fault current I″k3 = c U ÷ (√3 |Z|). Peak ip = κ √2 I″k, κ = 1.02 + 0.98 e−3R/X. Line-to-line I″k2 = (√3/2) I″k3.

Frequently asked questions

How do I calculate the short-circuit current of a transformer?
For a quick estimate, divide the full-load current by the impedance voltage: Ik ≈ In ÷ uk. A 1,000 kVA, 400 V transformer has In = 1,443 A; with uk = 6% the fault current is about 24 kA, or about 25 kA with the IEC voltage factor c = 1.05. Upstream network impedance lowers this slightly.
What is the difference between Ik and ip?
Ik (I″k) is the RMS value of the symmetrical short-circuit current, which breakers must interrupt. ip is the highest instantaneous value in the first half-cycle, including the DC offset. It decides the electromagnetic forces on busbars and the making capacity of switchgear. ip = κ × √2 × Ik, with κ between 1.02 and 2 depending on the X/R ratio.
How does cable length affect fault current?
Cable resistance adds to the loop impedance, so fault current falls with distance. A sub-board 150 m away on a single 95 mm² aluminium cable may see only 4–5 kA, even though the main board sees 15 kA. That is good for breaker ratings but must still be high enough to trip protection quickly.
What breaking capacity does a circuit breaker need?
The rated ultimate breaking capacity (Icu for IEC 60947-2 breakers, Icn for IEC 60898 MCBs) must be at least the prospective short-circuit current at the point of installation. Common ratings are 6, 10, 15, 25, 36, 50, 70 and 100 kA.
What is the voltage factor c in IEC 60909?
It accounts for the network running above nominal voltage. For maximum short-circuit currents in low-voltage systems IEC 60909-0 uses c = 1.05 where the voltage tolerance is ±6%, and 1.10 where it is ±10%. For minimum currents (used to check protection trips) c = 0.95.
Do motors contribute to short-circuit current?
Yes. Running induction motors feed the fault for a few cycles with roughly their locked-rotor current, typically 4–6 times their rated current. IEC 60909 requires adding them where they exceed about 5% of the fault current without motors. This calculator leaves them out.

Sources & references

  1. IEC 60909-0 — Short-circuit currents in three-phase AC systems: Calculation of currents
  2. IEEE Std 551 (Violet Book) — Calculating Short-Circuit Currents in Industrial and Commercial Power Systems
  3. Schneider Electric — Electrical Installation Guide, chapter G: Short-circuit current
  4. IEC 60947-2 — Low-voltage switchgear: Circuit-breakers