Why fault current matters
When phases short together, the only thing limiting the current is the impedance of the network between the source and the fault. Near a large transformer that can be tens of kiloamps. Every breaker and fuse must be able to interrupt the highest current it might see; if it cannot, it can explode instead of clearing the fault. Busbars and cable supports must also survive the peak electromagnetic forces of the first half-cycle. Fault current is therefore one of the first numbers in any LV design, alongside load current and voltage drop.
This calculator follows the IEC 60909 impedance method for a radial LV system: medium-voltage network, distribution transformer, then a cable run to a sub-board. It returns the maximum three-phase fault current at both points, the peak current, the line-to-line fault current and the minimum standard breaking capacity.
The formula
I″k3 = c·U ÷ (√3 · |Z_Q + Z_T + Z_C|) i_p = κ·√2·I″k3 κ = 1.02 + 0.98·e^(−3R/X) I″k2 = (√3 ÷ 2)·I″k3
U is the LV line voltage, ρ is 0.0178 Ω·mm²/m for copper and 0.0286 for aluminium (20 °C, as IEC 60909 requires for maximum currents), A is the cross-section, n the number of parallel cables per phase and x′ the cable reactance, about 0.08 mΩ/m for multicore cables.
Worked example
The defaults model a 1,000 kVA, 6% transformer (7.6 kW load losses) fed from a 250 MVA MV network, with a 400 V secondary feeding a sub-board through 60 m of two parallel 240 mm² copper cables.
- Network impedance referred to 400 V: 1.05 × 400² ÷ 250 MVA = 0.67 mΩ.
- Transformer impedance: 0.06 × 400² ÷ 1,000 kVA = 9.6 mΩ, of which R = 1.22 mΩ and X = 9.52 mΩ.
- At the LV terminals: |Z| ≈ 10.3 mΩ, so I″k3 = 1.05 × 400 ÷ (1.732 × 10.3 mΩ) ≈ 23.6 kA. With X/R ≈ 7.8, κ = 1.69 and the peak current is 56.5 kA.
- The cable adds 2.2 mΩ of resistance and 2.4 mΩ of reactance, and the fault current at the sub-board falls to 18.6 kA.
- The main LV breaker needs at least a 25 kA breaking capacity; devices at the sub-board need 20 kA.
The simple rule I_n ÷ u_k gives 24.1 kA, or 25.3 kA with c = 1.05, close to the full result because a 250 MVA network is stiff compared with a 1 MVA transformer.
Typical values at 400 V transformer terminals
| Transformer | u_k | Full-load current | I″k3 (infinite source, c = 1.05) |
|---|---|---|---|
| 250 kVA | 4% | 361 A | ≈ 9.5 kA |
| 400 kVA | 4% | 577 A | ≈ 15 kA |
| 630 kVA | 4% | 909 A | ≈ 24 kA |
| 1,000 kVA | 6% | 1,443 A | ≈ 25 kA |
| 1,600 kVA | 6% | 2,309 A | ≈ 40 kA |
| 2,500 kVA | 6% | 3,608 A | ≈ 63 kA |
Two transformers in parallel on one busbar roughly double the fault level, which is a common reason for switchgear upgrades.
How to read the results
- Ik3 at transformer terminals sets the breaking capacity of the main LV switchboard.
- Peak current ip is the value to check against the busbar system’s rated peak withstand current (Ipk).
- Ik3 at cable end sets the rating for downstream boards. The chart shows how fast fault current falls with distance.
- Line-to-line Ik2 is lower and is sometimes used to check that protection still trips fast enough.
Limitations
The result is the maximum symmetrical three-phase current. It leaves out motor contribution, generator sources, the transformer correction factor K_T (close to 1 for normal transformers), and conductor heating during the fault. Earth-fault current depends on the earthing system (TN, TT, IT) and zero-sequence impedance and needs its own calculation, especially for checking disconnection times. For final designs, use dedicated software or a full IEC 60909 or IEEE 551 study. Size the cable for load and voltage drop with the cable size calculator.
Method & assumptions
Source impedance ZQ = c U² ÷ S″kQ (X/R = 10). Transformer ZT = uk U² ÷ Sn, RT = Pk U² ÷ Sn². Cable R = ρ L ÷ (A × n), X = x′ L ÷ n. Symmetrical fault current I″k3 = c U ÷ (√3 |Z|). Peak ip = κ √2 I″k, κ = 1.02 + 0.98 e−3R/X. Line-to-line I″k2 = (√3/2) I″k3.
Frequently asked questions
How do I calculate the short-circuit current of a transformer?
What is the difference between Ik and ip?
How does cable length affect fault current?
What breaking capacity does a circuit breaker need?
What is the voltage factor c in IEC 60909?
Do motors contribute to short-circuit current?
Sources & references
- IEC 60909-0 — Short-circuit currents in three-phase AC systems: Calculation of currents
- IEEE Std 551 (Violet Book) — Calculating Short-Circuit Currents in Industrial and Commercial Power Systems
- Schneider Electric — Electrical Installation Guide, chapter G: Short-circuit current
- IEC 60947-2 — Low-voltage switchgear: Circuit-breakers