How this calculator sizes a generator
Sizing a generator set means passing three tests. The alternator must carry the running load continuously without overheating. It must hold the voltage within limits when the largest motor starts, because a direct-on-line motor briefly draws six to seven times its running current at a poor power factor. And the engine must pick up the power demanded during that start without stalling or dropping too far in speed.
The calculator computes the kVA each test requires, takes the largest, and rounds up to a standard genset size. It shows which test decided the size, so you can see whether a soft starter or a drive would let you buy a smaller set.
The formula
Motor running kVA = motor kW ÷ (η × PF) Motor starting kVA = running kVA × starting-current multiple
Voltage dip ≈ x″d × S_start ÷ (S_gen + x″d × S_start) → S_gen ≥ x″d × S_start × (1 − dip) ÷ dip
Engine kW at start = S_start × starting PF + other running kW ≤ 1.1 × (S_gen × 0.8)
Default starting-current multiples: 6.5 for direct-on-line, 2.2 for star-delta, 3.5 for soft starters and 1.2 for drives. The starting power factor of an induction motor on DOL is low, about 0.3–0.4, which is why the engine sees much less kW than the kVA figure suggests. The subtransient reactance x″d of small and medium alternators is typically 0.12–0.20 per unit.
Worked example
The defaults describe a 60 kW standby load at PF 0.85, 10% of it non-linear, with a 15 kW motor started direct-on-line, a 20% dip limit and a 15% design margin.
- Running load: 60 ÷ 0.85 = 70.6 kVA. With margin and the non-linear allowance: 70.6 × 1.15 × 1.05 = 85 kVA.
- Motor running kVA: 15 ÷ 0.78 = 19.2 kVA. Starting kVA at 6.5×: 125 kVA.
- Voltage dip test: 0.15 × 125 × 0.8 ÷ 0.2 = 75 kVA.
- Engine test: during the start the engine supplies 125 × 0.35 = 44 kW for the motor plus 45 kW for everything else, about 89 kW. An 80 kW (100 kVA) engine with 10% transient capacity gives only 88 kW, so the calculator moves up to 125 kVA.
Switch the starting method to a soft starter and the starting kVA falls to about 67 kVA. The engine test then needs 82 kVA and a 100 kVA set is enough. A drive brings it down to the running-load requirement of 85 kVA, still 100 kVA standard. This is the usual trade-off: the soft starter costs much less than the step up in generator size.
Typical starting current
| Starting method | Starting current | Starting torque | Comment |
|---|---|---|---|
| Direct-on-line | 6–7.5 × FLC | 150–250% | Simplest; hardest on generators |
| Star-delta | 2–2.5 × FLC | ≈ 33% of DOL | Current peak at changeover |
| Soft starter | 3–4 × FLC | adjustable | Good for pumps and fans |
| Variable-speed drive | 1–1.5 × FLC | up to 150% | Smallest generator; adds harmonics |
For North American motors, the NEMA code letter on the nameplate gives the locked-rotor kVA per horsepower, which you can turn into a multiple.
How to read the results
- Recommended generator is the standard kVA size that passes all three tests. Its kW rating is 80% of the kVA.
- Voltage dip on this set shows what the chosen generator will actually do when the motor starts. The bar chart colours sizes that meet your limit.
- Running load on the set should normally stay between 40% and 80%. Long running below 30% risks wet-stacking.
- Diesel use is a quick estimate at the running load. The generator fuel calculator gives the full fuel curve and cost per kWh.
Limitations
This is a screening method. Real voltage dip depends on the automatic voltage regulator, excitation system (PMG or shunt), engine governor and turbocharger response. Manufacturers’ sizing tools model these with tested motor-starting curves and ISO 8528-5 transient classes. Several motors starting together, lifts, X-ray machines and large UPS loads need special care. Altitude and high ambient temperature derate both engine and alternator. Use this result to shortlist a size, then confirm with the supplier.
Method & assumptions
Running kVA = kW ÷ PF, increased by the design margin, by 0–50% for non-linear loads and by 1/0.8 for prime duty. Motor starting kVA = motor kW ÷ (η × PF) × starting current multiple. Transient voltage dip ≈ x″d Sstart ÷ (Sgen + x″d Sstart), so the generator needed for a dip limit d is Sgen ≥ x″d Sstart (1 − d) ÷ d. The engine must also carry the kW during the start = Sstart × starting PF + other running kW, with up to 10% transient overload of its kW rating (kVA × 0.8). The chosen set is the next standard size above the largest requirement.
Frequently asked questions
How do I size a generator for my loads?
What size generator do I need to start a motor?
What is the difference between standby and prime generator ratings?
Why are generators rated in kVA and not kW?
How much voltage dip is acceptable when a motor starts?
Can I run a generator at very low load?
Sources & references
- ISO 8528-1 and 8528-5 — Reciprocating engine driven generating sets: ratings and transient performance
- IEEE Std 446 (Orange Book) — Emergency and Standby Power Systems
- NEMA MG 1 — Motors and Generators (locked-rotor kVA code letters)
- Caterpillar — Generator set sizing and motor starting (Application & Installation Guide)