District Heating Explained: How Heat Networks Work

How district heating networks work: generations 1G to 5G, heat sources, pipe losses, Denmark, Helsinki, China, and district cooling in Singapore and Malaysia.

Updated 6 min read 1,439 words

In Copenhagen, almost no one owns a boiler. Hot water arrives through underground pipes from a handful of plants: waste incinerators, biomass CHP stations, large heat pumps and, increasingly, giant tanks of stored heat. The same idea heats most of Helsinki, Stockholm, Reykjavik and large parts of northern China. District heating supplies roughly 9% of global heat demand in buildings, according to the IEA, and in some countries it is the default way to keep warm. This guide explains how the networks work, where the heat comes from and why cities from Denmark to Kuala Lumpur run versions of it.

Country heat data is on the heat dashboard, and the glossary entry on district heating has a short definition.

How a heat network works

A district heating system has three parts:

  1. Production. One or more central plants heat water. Large networks combine several sources and dispatch them by cost, much as a power grid does.
  2. Distribution. Pre-insulated steel pipes buried about a metre underground carry hot water out (supply) and cooler water back (return). Big cities have transmission mains of 500–1,000 mm diameter feeding smaller distribution pipes.
  3. Customer substations. Each building has a heat exchanger and a meter. Network water never enters the building’s radiators or taps; it passes heat through stainless steel plates.

The amount of heat delivered depends on the flow and the temperature drop between supply and return:

Heat delivered (kW) = flow (kg/s) × 4.19 kJ/kg·K × (T_supply − T_return)

Example: 80 °C supply, 45 °C return, 2 kg/s flow Q = 2 × 4.19 × 35 ≈ 293 kW (enough for roughly 40–60 flats on a cold winter day)

A low return temperature matters a lot. It lets the same pipe carry more heat, cuts losses and helps condensing boilers, heat pumps and flue gas condensation work better. Danish utilities often charge customers a penalty if their return water comes back too warm.

Five generations of district heating

Generation Era Carrier and supply temperature Typical heat source
1G 1880s–1930s Steam, >150 °C Coal boilers (New York’s steam system dates from 1882)
2G 1930s–1970s Pressurised hot water, >100 °C Coal and oil CHP; Soviet-era networks
3G 1970s–2000s Hot water 70–100 °C, pre-insulated pipes CHP, waste incineration, biomass
4G 2010s onward Hot water 50–70 °C Heat pumps, waste heat, solar thermal, storage
5G Emerging Ambient loop, ~10–25 °C Building-level heat pumps sharing heat and cold

Lower temperatures cut pipe losses and let more low-grade heat sources join. A 4G network at 55 °C can take heat straight from data centres, sewage heat pumps and solar thermal fields, which a 120 °C network could not use without boosting.

Where the heat comes from

The traditional workhorse is combined heat and power (CHP). A plant that only makes electricity throws away more than half its fuel energy as low-grade heat. A CHP plant sells that heat to the network and reaches total efficiencies of 80–90%. The shift now is towards sources that need no fossil fuel:

  • Waste incineration. Sweden and Denmark burn non-recyclable municipal waste for heat and power. Copenhagen’s Amager Bakke plant, with a ski slope on its roof, supplies district heat to roughly 150,000 households.
  • Large heat pumps. Seawater, sewage and river heat pumps of tens of megawatts are now common. Esbjerg in Denmark commissioned a seawater heat pump of about 70 MW in 2023 to replace a coal plant. With a COP of 3, each MWh of electricity gives about 3 MWh of heat. Compare running costs in the heat pump calculator.
  • Geothermal. Reykjavik’s network runs almost entirely on geothermal water. Paris, Munich and several Chinese cities tap deep aquifers. See Geothermal Energy Explained.
  • Solar thermal. Danish towns such as Dronninglund, Marstal and Vojens run large solar collector fields linked to pit storage.
  • Industrial and data centre waste heat. Refineries, steelworks, fertiliser plants and data centres all reject heat that a network can use.
  • Biomass boilers and CHP, mostly wood chips and pellets.

Thermal storage

Heat is cheap to store compared with electricity. Many networks use steel tanks holding a day or two of demand. Denmark has built pit thermal energy storage: lined, insulated pits holding 60,000–200,000 m³ of water that store summer solar heat for autumn and winter. Helsinki’s utility Helen has turned old underground oil caverns into large heat stores. Storage lets heat pumps and electric boilers run when electricity is cheap, which turns the heat network into a flexible load for the power grid (see demand response explained).

Country snapshots

Denmark. About 65% of households are connected, rising to almost all homes in Copenhagen. Danish law has required heat planning since the 1979 Heat Supply Act, utilities are mostly municipal or consumer-owned cooperatives that operate on a non-profit basis, and gas boilers in district heating areas are being phased out. Biomass, waste and heat pumps now supply most of the heat.

Sweden. District heating covers more than half of the heat market for homes and commercial buildings. Fossil fuels have fallen to a few percent of supply; the rest is biomass, waste, waste heat and heat pumps.

Finland. About 46% of the national heating market and around 90% of buildings in Helsinki are on district heat. Helsinki closed the Hanasaari coal plant in 2023 and stopped burning coal at Salmisaari in 2024, replacing them with heat pumps, electric boilers, biomass and storage.

China. Northern China has the world’s largest district heating systems, serving well over 10 billion m² of floor space according to government statistics. Coal still dominates, and coal-fired heating is a major cause of winter smog. Since 2017 a “clean heating” campaign has replaced many small coal boilers with gas, heat pumps and waste heat from power plants.

Eastern Europe and Russia. Many Soviet-era networks still run at high temperatures with large losses and poor metering. Poland, the Baltic states and Ukraine are among the larger systems, and modernisation is a major efficiency opportunity.

Losses, costs and pricing

Heat lost through the pipes rises with temperature difference and falls with pipe insulation and network density. Modern networks lose about 10–15% of heat produced. Old 2G networks can lose 20–30% or more. Heat density matters: a network serving dense flats needs far less pipe per MWh than one serving detached houses, which is why district heating suits cities better than suburbs.

District heat is a natural monopoly, because a building can only be connected to one network. Denmark requires heat to be sold at cost. Sweden and Finland rely on competition with heat pumps and on price dialogue processes. The UK, where networks serve only about 2–3% of heat, is bringing heat networks under Ofgem regulation from 2026. Compare district heat with other heating options in the heating cost comparison calculator.

District cooling in hot climates

In the tropics the same idea runs in reverse. A central plant chills water to about 4–6 °C, often with large high-efficiency chillers and overnight ice or chilled-water storage, and pipes it to office towers, malls and campuses. Central plants can reach better efficiency than many small rooftop units, take advantage of cheaper night-time electricity and free up building roof space.

  • Singapore runs one of the world’s largest underground district cooling networks at Marina Bay, operated by SP Group, serving the financial district and Marina Bay Sands area.
  • Malaysia: Gas District Cooling (GDC), a Petronas company, has supplied chilled water and electricity to the KLCC precinct since the late 1990s and runs similar plants in Putrajaya and at KLIA, using gas-fired turbines with absorption chillers that make use of waste heat.
  • The Gulf states have built large district cooling systems in Dubai, Abu Dhabi, Doha and Riyadh, where cooling makes up most of peak electricity demand.

For the building side of cooling, read air conditioning and cooling energy.

Quick summary

  • District heating moves heat from a few large sources to many buildings through insulated pipes.
  • Newer networks run cooler (50–70 °C or ambient), which cuts losses and lets heat pumps, waste heat and solar thermal in.
  • Denmark, Sweden, Finland and Iceland show how networks can run almost free of fossil fuels; China shows the scale, and the coal problem.
  • Losses of 10–15% are normal for modern networks; dense cities suit district heat best.
  • In hot climates the equivalent is district cooling, used in Singapore, Kuala Lumpur, Putrajaya and the Gulf.

Related reading: industrial heat explained, heat pumps explained and the world energy map.

Calculators for this topic

Frequently asked questions

What is district heating?
District heating is a network of insulated pipes that carries hot water (in old systems, steam) from central plants to many buildings. Each building has a heat exchanger instead of its own boiler. The heat can come from combined heat and power plants, waste incinerators, large heat pumps, geothermal wells, solar fields or industrial waste heat.
Which country uses the most district heating?
In Europe, Denmark leads with roughly two-thirds of households connected. Iceland is higher still, with about 90% of homes on geothermal district heating. By total size, China has the largest systems in the world, serving more than ten billion square metres of floor space in its northern provinces.
How much heat is lost in the pipes?
Modern, well-designed networks lose around 10 to 15% of the heat they send out. Older systems running at high temperatures can lose 20 to 30%, and some badly maintained networks in Eastern Europe and Central Asia lose even more.
Is district heating cheaper than a gas boiler?
It often is in countries with mature networks and cheap heat sources such as waste incineration, CHP or large heat pumps. In Denmark district heat is usually the cheapest option. Where networks are small or prices are set by monopoly operators, customers can pay more, which is why many countries regulate district heating prices.
What is district cooling?
District cooling works like district heating in reverse: a central plant chills water, often with large efficient chillers, seawater or thermal ice storage, and pipes it to buildings for air conditioning. Singapore's Marina Bay and Malaysia's KLCC and Putrajaya developments use district cooling.
What is fifth-generation district heating?
Fifth-generation networks circulate water at near-ambient temperatures, roughly 10 to 25 °C, and each building uses its own heat pump to raise or lower the temperature. The same loop can provide heating and cooling and share heat between buildings.

Sources & references

  1. Euroheat & Power: District Heating and Cooling Market Outlook
  2. Danish Energy Agency: Regulation and planning of district heating in Denmark
  3. IEA: District Heating (tracking report)
  4. Lund, H. et al. (2014). 4th Generation District Heating (4GDH). Energy 68
  5. Statistics Finland: Energy supply and consumption

Figures in this guide are typical ranges drawn from the sources above; your own numbers depend on location, prices and equipment. Use the linked calculators for site-specific estimates.