What heat rate tells you
Heat rate is the number power-plant engineers use instead of efficiency. It answers a practical question: how much fuel energy goes in for every kWh that leaves the plant fence? A plant with a heat rate of 7,000 Btu/kWh burns 7,000 Btu of fuel per kWh sent out. Because one kWh is 3,412 Btu, that plant turns 48.7% of its fuel into electricity and loses the rest as heat to the condenser, cooling tower and stack.
The two numbers carry the same information, but heat rate is easier to use for fuel accounting. Multiply it by generation and you have fuel burn; multiply by the fuel price and you have fuel cost per MWh. That is why traders talk about “spark spreads” and “dark spreads” computed from heat rate, and why utilities report heat rates to regulators.
This calculator converts in both directions, between five units, and on either heating-value basis. It then turns the result into physical fuel, cost and CO₂ for a plant of the size and capacity factor you enter.
The formula
η_HHV = η_LHV ÷ (HHV / LHV)
Fuel per MWh = HR (GJ/MWh, LHV) ÷ net calorific value CO₂ per MWh = HR (GJ/MWh, LHV) × emission factor (kg CO₂/GJ) Fuel cost = HR (GJ/MWh, LHV) × fuel price (per GJ)
The HHV/LHV ratios used are 1.108 for natural gas, 1.045 for bituminous coal, 1.06 for sub-bituminous coal and heavy fuel oil, and 1.09 for lignite and wood. Calorific values and emission factors are the IPCC 2006 defaults: 56.1 kg CO₂/GJ for gas, 94.6 for bituminous coal and 101 for lignite.
LHV or HHV: the trap in every comparison
The same gas turbine can be advertised at 41% efficiency in a European brochure and 37% in a US filing, and both figures are correct. The difference is the heating value. The higher heating value (HHV, gross) counts the latent heat of the water vapour formed in combustion; the lower heating value (LHV, net) does not. Power plants release that vapour through the stack, so LHV is the fairer measure of what the machine can do, and it is the IEA and European convention. The US EIA and most US utilities report HHV heat rates.
For natural gas, which contains a lot of hydrogen, the gap is large: an LHV efficiency of 55% is only 49.6% on an HHV basis. For coal the gap is small. Always check the basis before comparing two plants or two countries.
Worked example
The defaults describe a 400 MW combined-cycle gas plant at 55% net efficiency (LHV), running at a 55% capacity factor with gas at €8/GJ.
- Heat rate (LHV) = 3,600 ÷ 0.55 = 6,545 kJ/kWh, or 6,204 Btu/kWh.
- On an HHV basis efficiency falls to 55 ÷ 1.108 = 49.6%, and the heat rate becomes 6,874 Btu/kWh HHV.
- Each MWh needs 6.55 GJ of gas, about 190 m³ at 34.5 MJ/m³.
- Fuel cost is 6.55 × 8 = €52.4/MWh; CO₂ is 6.55 × 56.1 = 367 kg/MWh.
- Over a year the plant sends out 1,927 GWh, burns about 366 million m³ of gas (12.6 PJ) and emits 0.71 Mt of CO₂.
Change the fuel to sub-bituminous coal and enter a US-style 10,000 Btu/kWh HHV heat rate (one of the presets), and you get a 34% HHV (36% LHV) plant that needs about 0.53 t of coal and emits about 0.96 t CO₂ for every MWh.
Typical heat rates
| Technology | Net efficiency (LHV) | Heat rate (kJ/kWh, LHV) | Approx. Btu/kWh (HHV) |
|---|---|---|---|
| CCGT, H/J-class, new | 60–63% | 5,700–6,000 | 6,000–6,300 |
| CCGT, F-class | 55–58% | 6,200–6,550 | 6,500–6,900 |
| Aeroderivative gas turbine | 38–42% | 8,600–9,500 | 9,000–10,000 |
| Heavy-duty open-cycle GT | 34–38% | 9,500–10,600 | 10,000–11,200 |
| Ultra-supercritical coal | 42–45% | 8,000–8,600 | 8,000–8,500 |
| Subcritical coal (older) | 31–36% | 10,000–11,600 | 9,800–11,500 |
| Nuclear light-water reactor | 32–34% | 10,600–11,200 | ≈ 10,400 (EIA convention) |
Fleet averages are higher than the best values because plants run at part load, start and stop, and age. EIA’s annual heat-rate table is a good reality check for US plants.
How to read the results
- Heat rate (HHV) is the headline for US readers; the LHV figure in the hint and table suits IEA or European data.
- Fuel per MWh is the physical quantity a fuel buyer cares about: cubic metres of gas or kilograms of coal.
- Fuel cost per MWh is the short-run marginal cost of the plant before variable O&M and carbon. Compare it with power prices to see whether the plant is in the money.
- CO₂ per MWh follows directly from heat rate and fuel. Better efficiency is the only way to reduce it without changing fuel or capturing carbon.
Limitations
Heat rate changes with load, ambient temperature, cooling-water temperature and plant age. A single number is an average. Calorific values and CO₂ factors are IPCC defaults; coal in particular varies widely, so use your own fuel analysis where you can. For full plant economics use the LCOE calculator, for coal-specific tonnages the coal power plant calculator, and for gas turbines at part load the gas turbine fuel consumption calculator.
Method & assumptions
Efficiency η = 3,600 ÷ heat rate (kJ/kWh) = 3,412.14 ÷ heat rate (Btu/kWh). LHV and HHV efficiencies differ by the fuel's HHV/LHV ratio: ηHHV = ηLHV ÷ (HHV/LHV). Fuel per MWh = heat rate (GJ/MWh, LHV) ÷ net calorific value. CO₂ per MWh = GJ/MWh × emission factor (kg CO₂/GJ, IPCC 2006). Annual figures = net MW × 8,760 h × capacity factor.
Frequently asked questions
What is the heat rate of a power plant?
How do you convert heat rate to efficiency?
What is the difference between HHV and LHV heat rate?
What is a good heat rate for a combined-cycle gas plant?
What is the heat rate of a coal power plant?
How much fuel does a power plant burn per MWh?
Sources & references
- US EIA — Average operating heat rate for selected energy sources (Electric Power Annual, table 8.1)
- IPCC 2006 Guidelines for National GHG Inventories, Vol. 2 Energy, ch. 1 (calorific values and CO₂ factors)
- IEA — Energy Statistics Manual (gross and net calorific values)
- IPCC AR5 WGIII Annex III — Technology-specific cost and performance parameters
Embed this calculator
Free for blogs, installers, schools and NGOs. Copy the code below; it updates itself automatically.