Heating & gas calculator

Degree days calculator: heating and cooling demand

Calculates monthly heating and cooling degree days for a city or any point on Earth (NASA satellite climate data), then turns them into your building’s heat demand, peak heat load, fuel use and cost. Choose your own base temperatures in °C.

Editable share link Branded PDF report Free · no sign-up

Results

London, UK has about 1,844 heating degree days a year (base 15.5 °C) and 21 cooling degree days (base 22 °C). A building losing 180 W per kelvin needs about 7,968 kWh of heat a year and up to 4.6 kW on a cold day.
Heating degree days
1,844K·day/yr
base 15.5 °C · 3,320 °F·day
Cooling degree days
21K·day/yr
base 22 °C
Annual heat demand
7,968kWh
66 kWh/m²
Peak heat load (design day)
4.6kW
at -4.8 °C outside, 21 °C inside
Fuel / electricity for heating
8,853kWh
Heating cost per year
€885
Heat loss coefficient
180W/K
4.32 kWh per degree day
Mean annual temperature
11.4°C
climate normals
Degree days by month, London, UK
Monthly heat demand (kWh)

Month by month

MonthMean °CHDDCDDHeat kWhCost (€)
Jan5.231901,379153
Feb5.328601,234137
Mar7.624501,059118
Apr9.9170073482
May13.385036841
Jun16.528212214
Jul18.7109435
Aug18.5118495
Sep15.738116418
Oct12116050356
Nov82250973108
Dec5.531001,339149
  • Degree days are estimated from monthly mean temperatures with a statistical spread of daily temperatures around each month’s mean (as in the CIBSE TM41 / Hitchin approach). Values from daily weather records for a specific year can differ by 5–15%.
  • The base temperature is the outdoor temperature at which the building needs no heating because sun, people and appliances cover the losses. Well-insulated buildings have lower bases, which is why heat demand falls faster than the U-values alone suggest.
  • Pick “My location” to use NASA POWER satellite climatology for any point on the map.

How this degree days calculator works

The heat a building loses is proportional to the difference between inside and outside temperature, and to how long that difference lasts. Degree days capture both in one number for a climate. Once you know them, and how much heat your building loses per degree, the yearly heat demand is a single multiplication.

The calculator takes monthly mean temperatures from 1991–2020 climate normals for a list of cities, or from NASA POWER satellite climatology for any point you choose on the map. Monthly averages hide cold snaps and warm spells, so it spreads each month’s daily temperatures around the mean with a normal distribution (σ = 3.5 K), in the spirit of the Hitchin method described in CIBSE TM41. That way a month averaging 10 °C still collects some heating degree days on its colder days, even with a 10 °C base.

For the building, choose either floor area and insulation level (which sets a heat loss rate per m²) or enter a heat loss coefficient from an energy certificate or survey. The calculator then gives the yearly and monthly heat demand, the peak load on a cold day, the fuel needed and the cost.

The formula

HDD (month) = Σ days max(0, base − daily mean temperature) CDD (month) = Σ days max(0, daily mean − cooling base)

H (W/K) = floor area × specific loss (3.0 uninsulated … 0.25 passive house W/m²K) Heat demand (kWh) = H × HDD × 24 ÷ 1000 Peak load (kW) = H × (indoor − design temperature) ÷ 1000 Design temperature = coldest monthly mean − 10 °C

Fuel = heat demand ÷ efficiency; Cost = fuel × price

Worked example

With the defaults: London, heating base 15.5 °C, cooling base 22 °C, a 120 m² house with average insulation (1.5 W/m²K), so H = 180 W/K, heated by a 90% gas boiler at €0.10/kWh.

  • London’s monthly means run from 5.2 °C in January to 18.7 °C in July (11.4 °C annual mean). That gives about 1,844 heating degree days (3,320 °F·days) and only 21 cooling degree days.
  • Each degree day costs the house 180 × 24 ÷ 1000 = 4.32 kWh of heat.
  • Yearly heat demand: 4.32 × 1,844 ≈ 7,970 kWh, or 66 kWh per m².
  • Peak load: the design temperature is 5.2 − 10 = −4.8 °C, so 180 × (21 + 4.8) ÷ 1000 ≈ 4.6 kW.
  • Fuel: 7,970 ÷ 0.90 ≈ 8,850 kWh of gas, costing about €885 a year.

January alone needs about 1,380 kWh of heat; July about 43 kWh.

How to read the results

  • Heating degree days is the climate’s heating severity at your chosen base. Compare cities only at the same base.
  • Annual heat demand is useful heat, before boiler or heat pump losses.
  • Peak heat load is what a boiler or heat pump must deliver on a cold day. It is the figure installers use for sizing; oversizing beyond it adds cost and, for heat pumps, cycling.
  • kWh per degree day in the heat loss hint is your building’s weather-corrected fingerprint for tracking bills across years.

Typical values

City HDD, base 15.5 °C (approx.) CDD, base 22 °C (approx.)
Madrid 1,200–1,500 250–400
London 1,800–2,000 under 50
Berlin 2,300–2,500 under 50
Chicago 2,700–3,100 150–250
Stockholm 3,000–3,300 under 30
Kuala Lumpur 0 over 2,000
Insulation level Specific heat loss (W/m²K of floor)
Uninsulated, pre-1950 3.0
Average, some upgrades 1.5
Good, post-2000 code 1.0
Passive house 0.25

Tips for using degree days well

  • Match the base to the building. A well-insulated home with lots of appliances may not need heat until 12–14 °C outside; using 15.5 °C would overstate its demand.
  • Calibrate with your bills. Divide last winter’s heating energy by the degree days for the same months and compare with the calculator’s kWh per degree day.
  • Size heating from the peak, not the annual total. Then check running costs with the heat pump calculator or heating cost comparison.
  • Test upgrades. Change the insulation level to see how much demand and peak load fall, then price the work with insulation savings.

Limitations

Degree days estimated from monthly means are typically within 5–15% of values from daily weather records, and any single year can differ from the long-term normal by a similar amount. The heat loss model ignores solar gains beyond what the base temperature captures, thermal mass and ventilation habits. The cooling figure is a sensible-heat estimate without solar and internal gains or humidity, so it understates real air-conditioning loads. NASA satellite climatology has a resolution of about 50 km and can miss local effects such as cities, valleys and coasts.

Method & assumptions

HDD for a month = Σ over the days of max(0, base − daily mean), estimated from the monthly mean with a normal distribution of daily means (σ = 3.5 K). Annual heat demand = heat loss coefficient H (W/K) × HDD × 24 ÷ 1000. H = floor area × specific loss for the insulation level (3.0 W/m²K uninsulated … 0.25 passive house). Peak load = H × (indoor − design temperature), design temperature = coldest monthly mean − 10 °C. Fuel = heat ÷ efficiency.

Frequently asked questions

What are heating degree days?
Heating degree days (HDD) measure how much, and for how long, the outdoor temperature stays below a base temperature. A day averaging 5 °C against a 15.5 °C base adds 10.5 degree days. Summed over a year, they are proportional to the heat a building needs, which is why energy managers use them to compare winters and buildings.
What base temperature should I use?
The UK and much of Europe use 15.5 °C, the US uses 65 °F (18.3 °C). The right base for your building is the outdoor temperature at which it needs no heating: lower for well-insulated buildings with high internal gains (12–14 °C), higher for old, leaky ones or warmer thermostats.
How do I calculate heat demand from degree days?
Multiply the building's heat loss coefficient (W/K) by the degree days and by 24 hours, then divide by 1,000 to get kWh. A house losing 180 W per kelvin in a 1,844 degree-day climate needs 180 × 1,844 × 24 ÷ 1,000 ≈ 7,970 kWh of heat a year.
How many heating degree days does London have?
Around 1,800–2,000 a year at a 15.5 °C base, depending on the period. Using 1991–2020 monthly normals, this calculator gives about 1,840. Berlin has roughly 2,400 and Stockholm over 3,000 at the same base.
What are cooling degree days used for?
Cooling degree days (CDD) do the same job for air conditioning: they add up how far and how long the temperature stays above a base, often 18.3 °C or 22 °C. Hot humid cities such as Kuala Lumpur have well over 2,000 CDD at a 22 °C base and almost no heating degree days.
How do I compare my heating bills between a mild and a cold winter?
Divide the energy used by the degree days of the same period. The resulting kWh per degree day is a weather-corrected measure of your building's performance; if it falls after insulating, the saving is real and not just a mild winter.

Sources & references

  1. CIBSE TM41: Degree-days, theory and application
  2. Degree Days.net: Degree days, handle with care
  3. NASA POWER: Prediction of Worldwide Energy Resources (climate data)