Glossary · Grid & markets

Under-frequency load shedding (UFLS)

Automatic disconnection of blocks of customer demand when grid frequency falls below set thresholds, to prevent a total collapse.

UFLS relays are a last line of defence. In Continental Europe shedding starts at 49.0 Hz and steps up so that about 45% of load can be cut by 48.0 Hz. Great Britain’s scheme starts at 48.8 Hz; Texas’s ERCOT begins at 59.3 Hz on its 60 Hz grid.

In Britain on 9 August 2019, a lightning strike followed by the loss of a wind farm and a gas plant pushed frequency to 48.8 Hz; UFLS disconnected about 1 million customers for under an hour, but the grid survived. See blackout.