Rate of change of frequency (RoCoF)
How fast grid frequency rises or falls after a sudden imbalance, in hertz per second; lower system inertia means faster changes.
When a large plant trips, frequency starts falling at a rate set by the size of the loss and the inertia of spinning machines. High RoCoF can trigger protection relays that disconnect embedded generators, making the event worse. Great Britain relaxed loss-of-mains settings on small generators from 0.125 Hz/s to 1 Hz/s after the August 2019 blackout.
Grids with high shares of inverter-based solar and wind manage RoCoF with synchronous condensers, grid-forming inverters and very fast battery response. See grid frequency and balancing.
Related terms
All terms →- Inertia (grid)
The kinetic energy stored in synchronously rotating generators and motors that resists sudden changes in grid frequency.
- Grid frequency
The rate at which alternating current changes direction on a power system, 50 Hz or 60 Hz, which reflects the instantaneous balance of supply and demand.
- Frequency response
The automatic change in generation or load that arrests and corrects a frequency deviation after a sudden imbalance on the grid.
- Frequency containment reserve (FCR)
The fastest automatic balancing reserve in Europe, which responds within seconds to stop a frequency deviation from growing.