Results

The prospective three-phase fault current is 23.6 kA at the transformer LV terminals (peak 56.5 kA) and 18.6 kA at the cable end. Protective devices need a breaking capacity of at least 25 kA at the main board and 20 kA at the end of the cable.
Ik3 at transformer terminals
23.6kA
25.3 kA with an infinite source
Peak current ip (terminals)
56.5kA
κ = 1.69
Ik3 at cable end
18.6kA
Peak current ip (cable end)
37.9kA
Line-to-line fault Ik2 (cable end)
16.1kA
Transformer full-load current
1,443A
Breaking capacity, main board
25kA
next standard Icu/Icn
Breaking capacity, cable end
20kA
Fault current vs cable length

Impedance per phase (referred to LV)

ElementR (mΩ)X (mΩ)Z (mΩ)
Upstream network0.070.670.67
Transformer1.229.529.6
Cable2.232.43.27
Total to cable end3.5112.5913.07
  • Maximum three-phase symmetrical fault current per IEC 60909-0 with voltage factor c and conductors at 20 °C. Motor contribution and the transformer correction factor KT are neglected (KT is close to 1 for uk ≤ 6%).
  • Single-phase earth-fault current depends on the zero-sequence impedance and the earthing system; at the transformer terminals of a Dyn unit it is about the same as Ik3, and it falls faster along the cable.