Lifting 250 kW from PF 0.78 to 0.95 needs 118.4 kVAr of capacitors (a 125 kVAr bank). Current drops from 463 A to 380 A, freeing 57 kVA of supply capacity. Savings of about 786 € a month pay back the bank in 4.8 months.
Capacitor required
118.4kVAr
nearest standard bank: 125 kVAr
Capacitance per phase (delta)
785µF
2,355 µF per phase in star
Current before
463A
Current after
380A
−18%
Apparent power before
321kVA
Apparent power after
263kVA
Reactive power before
201kVAr
82 kVAr after
Cut in I²R losses
33%
Tariff saving per month
€688
57.4 kVA less maximum demand
Loss saving per month
€97.76
Capacitor bank cost
€3,750
Simple payback
4.8months
9,432 € saved per year
kVAr per kW multiplier (tan φ1 − tan φ2)
| Present PF | to 0.9 | to 0.92 | to 0.95 | to 0.98 | to 1 |
|---|---|---|---|---|---|
| 0.6 | 0.849 | 0.907 | 1.005 | 1.13 | 1.333 |
| 0.65 | 0.685 | 0.743 | 0.84 | 0.966 | 1.169 |
| 0.7 | 0.536 | 0.594 | 0.692 | 0.817 | 1.02 |
| 0.75 | 0.398 | 0.456 | 0.553 | 0.679 | 0.882 |
| 0.8 | 0.266 | 0.324 | 0.421 | 0.547 | 0.75 |
| 0.85 | 0.135 | 0.194 | 0.291 | 0.417 | 0.62 |
| 0.9 | — | 0.058 | 0.156 | 0.281 | 0.484 |
- Where many variable-speed drives, inverters or other harmonic sources are present, use detuned (reactor-protected) capacitor banks or active filters to avoid resonance.
- Correct to 0.95–0.98 rather than 1.0: at light load a fixed bank can push the PF leading and raise the voltage. Automatic stepped banks track the load.