Recommended: a standby-rated generator of 125 kVA (100 kW at PF 0.8). The running load needs 85 kVA with margin, and starting the 15 kW motor draws about 125 kVA, which causes a 13% voltage dip on this set. The deciding factor is engine load during the start.
Recommended generator
125kVA
100 kW at PF 0.8, standby
Running load
71kVA
60 kW at PF 0.85
Required for running load
85kVA
margin, non-linear loads and duty included
Motor starting kVA
125kVA
6.5 × 19.2 kVA running
Required for voltage dip
75kVA
dip limit 20%
Voltage dip on this set
13%
Engine load during start
89kW
needs at least 101 kVA
Running load on the set
56%
Diesel use at running load
23L/h
Starting methods for this motor
| Method | Starting current | Starting kVA | Generator for the dip limit (kVA) |
|---|---|---|---|
| Direct-on-line (DOL) | 6.5 × FLC | 125 | 100 |
| Star-delta | 2.2 × FLC | 42 | 100 |
| Soft starter | 3.5 × FLC | 67 | 100 |
| Variable-speed drive (VFD) | 1.2 × FLC | 23 | 100 |
- Screening method: the voltage-dip formula uses the alternator subtransient reactance and ignores the voltage regulator response and engine speed dip. Confirm with the manufacturer's sizing software (motor starting curves, transient response class per ISO 8528-5).
- If several motors can start at once, enter their combined kW as the largest motor. Sequencing starts, soft starters or drives usually allow a much smaller generator.