At 80% load and 25 °C the unit delivers 343.8 MW and burns 2,375 MMBtu of gas per hour (64,920 m³/h). Part-load efficiency is 54.7% LHV (heat rate 6,909 Btu/kWh HHV), so fuel costs 55.3 € per MWh.
Gas consumption
2,375MMBtu/h
2,506 GJ/h (HHV)
Volume flow
64,920m³/h
55.02 million scf per day
Mass flow
50.6t/h
Electrical output
343.8MW
available at 25 °C: 429.8 MW
Efficiency at this point (LHV)
54.7%
Heat rate (HHV)
6,909Btu/kWh
6,578 kJ/kWh LHV
Fuel cost per MWh
55.3€/MWh
CO₂ per MWh
367kg
Annual gas use
11.88million MMBtu
0.325 billion m³ · 11.46 Bcf
Annual generation
1,719GWh
Annual fuel + carbon cost
95million €
Annual CO₂
630kt
Part-load table
| Load | Output (MW) | Efficiency (LHV) | Heat rate (Btu/kWh HHV) | MMBtu/h | m³/h | €/MWh |
|---|---|---|---|---|---|---|
| 30% | 128.9 | 44% | 8,585 | 1,107 | 30,254 | 68.7 |
| 40% | 171.9 | 47.8% | 7,915 | 1,361 | 37,187 | 63.3 |
| 50% | 214.9 | 50.3% | 7,512 | 1,614 | 44,121 | 60.1 |
| 60% | 257.9 | 52.2% | 7,244 | 1,868 | 51,054 | 58 |
| 70% | 300.8 | 53.6% | 7,052 | 2,122 | 57,987 | 56.4 |
| 80% | 343.8 | 54.7% | 6,909 | 2,375 | 64,920 | 55.3 |
| 90% | 386.8 | 55.6% | 6,797 | 2,629 | 71,854 | 54.4 |
| 100% | 429.8 | 56.4% | 6,707 | 2,882 | 78,787 | 53.7 |
- Part-load and ambient corrections are generic curves for screening. Manufacturer correction curves (output, heat rate vs load, temperature, humidity, altitude) give exact values.
- CO₂ factor 53.06 kg/MMBtu HHV (US EPA). Gas density assumed 0.78 kg/m³; m³ at 15 °C, 1 atm.