Results

London, UK has about 1,844 heating degree days a year (base 15.5 °C) and 21 cooling degree days (base 22 °C). A building losing 180 W per kelvin needs about 7,968 kWh of heat a year and up to 4.6 kW on a cold day.
Heating degree days
1,844K·day/yr
base 15.5 °C · 3,320 °F·day
Cooling degree days
21K·day/yr
base 22 °C
Annual heat demand
7,968kWh
66 kWh/m²
Peak heat load (design day)
4.6kW
at -4.8 °C outside, 21 °C inside
Fuel / electricity for heating
8,853kWh
Heating cost per year
€885
Heat loss coefficient
180W/K
4.32 kWh per degree day
Mean annual temperature
11.4°C
climate normals
Degree days by month, London, UK
Monthly heat demand (kWh)

Month by month

MonthMean °CHDDCDDHeat kWhCost (€)
Jan5.231901,379153
Feb5.328601,234137
Mar7.624501,059118
Apr9.9170073482
May13.385036841
Jun16.528212214
Jul18.7109435
Aug18.5118495
Sep15.738116418
Oct12116050356
Nov82250973108
Dec5.531001,339149
  • Degree days are estimated from monthly mean temperatures with a statistical spread of daily temperatures around each month’s mean (as in the CIBSE TM41 / Hitchin approach). Values from daily weather records for a specific year can differ by 5–15%.
  • The base temperature is the outdoor temperature at which the building needs no heating because sun, people and appliances cover the losses. Well-insulated buildings have lower bases, which is why heat demand falls faster than the U-values alone suggest.
  • Pick “My location” to use NASA POWER satellite climatology for any point on the map.

Free calculator by Energy.co.my