PUE is 1.48: for every kWh used by IT equipment, the facility draws 1.48 kWh in total. Annual consumption is 12,970 MWh, of which 4,210 MWh is overhead, costing 505,247 €. At a PUE of 1.3 the same IT load would save 189,887 € and 725 t CO₂ a year.
PUE
1.48
DCiE 67.5%
Facility power
1,481kW
Annual energy
12,970MWh
8,760 MWh for IT
Annual electricity cost
1.6million €
Cost of overhead
€505,247
cooling, power losses, building
Cost per kW of IT per year
€1,556
Saving at target PUE
€189,887
1,582 MWh per year
CO₂ per year
5,940t
Water per year
15,768m³
WUE 1.8 L/kWh
Energy balance
| Component | kW | MWh/yr | Share |
|---|---|---|---|
| IT equipment | 1,000 | 8,760 | 67.5% |
| Cooling | 375.5 | 3,290 | 25.4% |
| UPS losses | 65.1 | 570 | 4.4% |
| Transformers & PDUs | 20 | 175 | 1.4% |
| Lighting & other | 20 | 175 | 1.4% |
- PUE per ISO/IEC 30134-2 is measured over a full year at the facility meter; this tool uses average powers. With a known PUE the overhead split shown is illustrative (70% cooling).
- Water use depends heavily on the cooling design and climate; enter your WUE (ISO/IEC 30134-9). CO₂ uses the selected country's average grid intensity.