The plant delivers 1,462,500 ton-hours of cooling a year and uses 1,608,750 kWh (1.1 kW/TR including auxiliaries), costing 225,225 €. A chiller at 0.52 kW/TR would save 67,568 € a year and pay back in 3.3 years.
Annual electricity cost
€225,225
1,608,750 kWh per year
Chiller COP
4.14
EER 14.1 Btu/Wh
Plant efficiency
1.1kW/TR
plant COP 3.2
Cooling capacity
1,758kW
500 TR
Average electrical demand
358kW
Cost per ton-hour
0.154€/TRh
Annual saving with new chiller
€67,568
482,625 kWh
Simple payback
3.3years
CO₂ per year
968t
291 t saved with the upgrade
Efficiency conversions
| kW/TR | COP | EER (Btu/Wh) | Cost per year (€) |
|---|---|---|---|
| 0.45 | 7.82 | 26.7 | 143,325 |
| 0.5 | 7.03 | 24 | 153,563 |
| 0.55 | 6.39 | 21.8 | 163,800 |
| 0.6 | 5.86 | 20 | 174,038 |
| 0.7 | 5.02 | 17.1 | 194,513 |
| 0.8 | 4.4 | 15 | 214,988 |
| 1 | 3.52 | 12 | 255,938 |
| 1.2 | 2.93 | 10 | 296,888 |
- Uses one average kW/TR. Chillers are more efficient at part load and with cooler condenser water; for a detailed estimate use the IPLV/NPLV or an hourly load profile.
- CO₂ uses the selected country's average grid intensity (lifecycle, OWID/Ember).